Type 2 AC surge protector - 1-pole - pluggable
Part Number: 821120921
DAC50GS-10-1300DC
- Type 2 AC surge protector
- In: 20 kA
- Imax: 50 kA
- Pluggable module for each phase
- Remote signaling
- EN 61643-11, IEC 61643-11 compliance
These SPDs are based on high energy GSG equipped with thermal disconnector and failure indicator, to comply with standards and to provide a maximum protection efficiency, an high impulse current capability and a improved reliability.
The SPD for the phase voltage transformer(PT) is installed in the terminal box of the switching field.
The neutral line(N phase) of each secondary winding is connected to only one SPD in series with the ground.
|
SPD type
|
IEC | 2 |
|
Max. AC operating voltage
|
Uc | 255 Vac |
|
Residual Current
Leakage current to Ground
|
Ipe | None |
|
DC sparkover voltage (100V/s)
|
1300Vdc |
|
|
Follow current
|
If | Yes |
|
Follow current interrupting capability
|
Ifi |
|
|
Nominal discharge current
15 x 8/20 µs impulses
|
In | 15 kA |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 30 kA |
|
Protection level N/PE
@ In (8/20µs) and @ 6 kV (1,2/50 µs)
|
Up N/PE | 2.2 kV |
|
Technology
|
Gas discharge tube |
|
|
SPD configuration
|
Single phase |
|
|
Connection to Network
|
By screw terminals: 2.5-25mm² |
|
|
Format
|
Plug-in modular box |
|
|
Plugable
|
Yes |
|
|
Mounting
|
Symmetrical rail 35 mm (EN 60715) |
|
|
Housing material
|
Thermoplastic UL94 V-0 |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Protection rating
|
IP20 |
|
|
Failsafe mode
|
Disconnection from AC network |
|
|
Disconnection indicator
|
1 mechanical indicator by pole - Red/Green |
|
|
Spare module(s)
|
MDAC50G-1300DC |
|
|
Remote signaling of disconnection
|
Output on changeover contact |
|
|
Wiring for remote signaling
|
1.5 mm² max. |
|
|
Max. Voltage/Current for remote signaling
|
250 V / 0.5 A (AC) / 30 V / 3 A (DC) |
|
|
Dimensions
|
See diagram |
|
Standards compliance
|
IEC 61643-11 / EN 61643-11 |
|
Thermal disconnector
|
Internal |
|
|
Installation ground fault breaker
|
Type 'S' or delayed |
|
|
Back-up protection device
|
50 A min. - 125 A max. - Fuses Type gG |
Datasheet
CCA